![]() INVERTER LS200A MODE | |
| Innovatory unique outstanding and perfect | |
| Space vector design: | |
| Space vector voltage module with unique style | |
| Silent design: | |
| IGBT module, high load wave, high speed switching with silent | |
| Smooth current: | |
| Trending Sin wave, motor smooth rotation without vibration and safety | |
| Safety design: | |
| Reducing confused/mixed message transference and restraining | |
| transmission and radiant wave | |
| Bright appearance: | |
| Aluminum made outer shell, with light and efficient measurement and | |
| excellent cooling capacity, strong and durable | |
| Low price level: | |
| It is competitive for low price level market with good potential for | |
| transmission equipment | |
![]() |
![]() |
![]() | ||
|
LS200A
Inverter |
Speed
Meter |
Potentiometer |
![]() |
Red
locus Curve of normal current output Yellow
locus Blue
locus |
Standard Specifications
| Voltage | 200V(Single) | ||||
| Model |
LS200A-20-5 |
LS200A-2001S |
LS200A-2002S | ||
|
MAX Motor(KW) |
0.4 |
0.75 |
1.5 | ||
|
Control Characteristics |
Rated Output Capacity |
1.2 |
1.7 |
2.8 | |
|
Rated Output AMP. |
3 |
4.5 |
7.5 | ||
|
MAX. Output Voltage |
200V~240V Three phase matched voltage | ||||
|
Power Source |
Highest Output Frequency | Up to 120Hz by Analog setting | |||
| Rated Voltage Variance | 200/208/220/240V 60Hz | ||||
| Allow Voltage Variance | |||||
| Control System | Control Principle | SV PWM sine wave, voltage space vector control | |||
| Range of Frequency Control | 1~120Hz | ||||
| Frequency Precision | Analog Command:0.1%(25oC |
||||
|
Frequency Resolution |
Analog operator:0.1Hz | ||||
|
Output FRE. Resolution |
0.1Hz | ||||
|
Overload Limited |
Rated Output AMP.150%, 60Sec. | ||||
|
Signal of Frequency Setting |
DC 0~5V | ||||
|
Time for Speed Acc/Dec. |
Individual Setting Second speed setting acc/dec in the meantime | ||||
|
Torque for Braking |
About 20% | ||||
|
V/F Curve |
Automatic torque compensation or compensation by any V/F curve setting. | ||||
|
Protection Function |
Instantaneous Over Current |
Output stop for 200% rated current | |||
|
Overload |
Above 150% rated current, output stopped in 60 sec. | ||||
|
Over-Voltage or Low-Voltage |
Main & return DC lines voltage above 400V or under AC 200V 1 phase 170V)output stopped | ||||
|
Instantaneous Power Break |
Stop over 15ms | ||||
|
Ventilation Over-Heat |
Protected by thermo-switch | ||||
|
Charging Indication |
Main & return DC lines voltage above 50V,charging lamp is on light | ||||
| Rotation System |
Input |
Rotation |
FWD & REV rotation or individual command | ||
|
Recovery |
Upon removal of protection action signal | ||||
|
Multi-Function Input |
Second speed control via terminal point | ||||
|
Output |
Analog Voltage |
Analog Voltage Output DC 0~5V | |||
|
Abnormal Contact |
Abnormal output contact(addendum function) | ||||
|
Display |
Abnormal LED Display |
Abnormal function display for Run/Stop yellow: power on . Red: fault motion Green: starting run | |||
|
Environment |
Location |
In door, no corrosive gas or liquid and free from dust | |||
|
Ambient Temperature |
10~+40oC(not frozen) | ||||
|
Storage Temp. |
-15oC~40oC(avoiding high temperature to damage capacitor in main line) | ||||
|
Humidity |
Below dew point, up to 90%RH | ||||
|
Vibration |
Below0.5G | ||||
|
Main Circuit Wiring | |||||
![]() |
|||||
|
Terminal Wiring
Meyhod | |||||
![]() |
|||||